Battery Voltage Monitoring
Parameter 195
Batt.undervolt.
V < 00.0V
Battery voltage monitoring: Threshold value 9.5 to 30.0 V
If the monitored battery voltage falls below the configured percentage of the confi-
gured threshold for at least the delay time configured in Parameter 196, an F1 class
alarm
is issued.
Issuing of F1 class alarm
Parameter 196
Batt.undervolt.
delay 00s
Battery undervoltage delay 0 to 99 s
For the control unit to recognize a battery undervoltage fault condition, the thre-
shold value configured in Parameter 195 must be exceeded without interruption for
t
his period of time.
Note: Regardless of the configured battery voltage monitoring threshold, readiness
for operation is withdrawn and an alarm message is issued if the power supply vol-
tage falls below 9 Vdc during normal operation or if the power supply voltage falls
below 11 Vdc during the start sequence.
Time Of Active Horn
Parameter 197
Horn self reset
0000s
Horn acknowledgment after 1 to 9.999 s
The horn (centralized alarm) will remain active for the time configured and then
deactivate (acknowledged) automatically.