Manual 37364A GCP-30 Packages - Genset Control
Alarm Inputs
The discrete inputs can be connected in positive or negative logic:
positive logic The DI is connected to +4
to 40Vdc and common is connected to chassis ground/batt. negative.
negative logic The DI is connected to chassis ground/batt. negative and common is connected to +4 to 40Vdc.
Positive Logic
Signal device
Discrete input
AB
+/-4 to 40 Vdc
Figure 5-9: Discrete inputs - Alarm inputs - positive logic
Terminal Associated
Common
Description
(according to DIN 40 719 Part 3, 5.8.3)
A
max
A B
34
33
Discrete input [D01]
- Alarm input
- In Sprinkler operation: EMERGENCY STOP
2.5 mm²
35
Discrete input [D02]
- Alarm input
2.5 mm²
36
Discrete input [D03]
- Alarm input
2.5 mm²
61
60
Discrete input [D04]
- Alarm input
- If discrete input terminal 34 is not available in Sprinkler operation:
EMERGENCY STOP
2.5 mm²
62
Discrete input [D05]
- Alarm input or
- Firing speed reached ("Generator")
2.5 mm²
63
Discrete input [D06]
- Alarm input or
- Operation mode selector blocked
2.5 mm²
64
Discrete input [D07]
- Alarm input or
- Change breaker logic
2.5 mm²
65
Discrete input [D08]
- Alarm input
2.5 mm²
66
Discrete input [D09]
- Alarm input
2.5 mm²
67
Discrete input [D10]
- Alarm input or
- 'Close GCB' before expiration of delayed engine monitoring
2.5 mm²
68
Discrete input [D11]
- Alarm input or
- Inhibition emergency power (from software version 4.3010 or higher)
2.5 mm²
69
Discrete input [D12]
- Alarm input
2.5 mm²
70
Discrete input [D13]
- Alarm input or
- No-load operation mode
2.5 mm²
71
Discrete input [D14]
- Alarm input
2.5 mm²
72
Discrete input [D15]
- Alarm input
2.5 mm²
73
Discrete input [D16]
- Alarm input
2.5 mm²
Page 30/46 © Woodward
Table 5-10: Terminal assignment - alarm inputs positive logic