Manual 37364A GCP-30 Packages - Genset Control
Analog Inputs (XPD, XPQ)
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
WARNING
The analog inputs of the GCP are not isolated. When utilizing an isolation monitor, use of two-pole, iso-
lated transmitters is recommended.
The analog inputs for active transmitters (0 to 20 mA, 0 to 10V) should only be operated with two-pole,
isolated transmitters.
GND
CC AB
C
A
a
I
B
AB
Analog input
VDO 0 to 180/380 Ohm
Analog input
0/4 to 20 mA
Analog input
Pt100
Figure 5-11: Analog inputs
Terminal Description
(according to DIN 40 719 Part 3, 5.8.3)
A
max
A B C
93 94 95 Analog input 1 [T1]
0/4 to 20 mA, configurable function:
- Alarm input / Set value input / Actual value input
1.5 mm²
96 97 98 Analog input 2 [T2]
0/4 to 20 mA, configurable function:
- Alarm input / Set value input / Actual value input
1.5 mm²
99 100 101 Analog input 3 [T3]
0/4 to 20 mA, configurable function:
- Alarm input / Set value input / Actual value input
1.5 mm²
102 103 104 Analog input 4 [T4]
Pt100, configurable function:
- Alarm input / Actual value input
1.5 mm²
105 106 107 Analog input 5 [T5]
Pt100, configurable function:
- Alarm input / Actual value input
1.5 mm²
108 109 - Analog input 6 [T6]
VDO pressure 0 to 180 Ω (0 to 5/10 bar or 0 to
72.5/145 psi), configurable function:
- Alarm input / Actual value input
1.5 mm²
111 112 - Analog input 7 [T7]
VDO temperature 0 to 380 Ω (30 to 120°C or 86 to
248°F), configurable function:
- Alarm input / Actual value input
1.5 mm²