Manual 37364A GCP-30 Packages - Genset Control
Analog Outputs (XPD, XPQ)
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Analog output
0 V
A
B A
I
Figure 5-16: Analog outputs
Ia GND Description A
max
A B
120 121 Analog output [A1] - 0/4 to 20 mA 1.5 mm²
122 123 Analog output [A2] - 0/4 to 20 mA 1.5 mm²
Table 5-18: Analog outputs - terminal assignment
Controller Outputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The voltage and speed controller outputs in the XPD Package are three-position contacts [made up of a chan-
geover contact and a normally open contact]. The voltage and speed controller outputs in the BPQ and
XPQ Packages are configurable as voltage, current, or PWM output signals.
Three-Position Controller (XPD)
The three-position controller is only included in the XPD Package.
11 12 13
Voltage / power factor
controller
Common
Raise
Lower
Voltage / power
factor controller
8
Common
Speed / power
controller
Speed / power
controller
max. 250 V AC
9 10
Lower
Raise
Figure 5-17: Controller - Three-position controller
Terminal Description A
max
8 common
Speed controller (n/f) / Power controller (P)
2.5 mm²
9 raise 2.5 mm²
10 lower 2.5 mm²
11 common
Voltage controller (V) / Reactive power controller (Q)
2.5 mm²
12 raise 2.5 mm²
13 lower 2.5 mm²
Table 5-19: Controller outputs - terminal assignment
Page 36/46 © Woodward