The alarm must be acknowledged and
reset by manually pressing the
appropriate buttons or by activating
the LogicsManager output "External
acknowledgement" (via a discrete
input or via an interface).
3056 Monitoring lockable 2 Yes Monitoring for fault conditions is only
performed if "Lock Monitoring Status
24.40" is false.
[No] Monitoring for this fault condition is
continuously enabled regardless of
"Lock Monitoring Status 24.40".
4.3.1.4 df/dt (ROCOF)
General notes
df/dt (rate of change of frequency) monitoring measures the stability of the frequency.
The frequency of a source will vary due to changing loads and other eects. The rate of
these frequency changes due to the load variances is relatively high compared to those of
a large network.
Function "Rate of change of frequency not within permissible limits"
The control unit calculates the unit of measure per unit of time. The df/dt is measured
over 4 sine waves to ensure that it is dierentiated from a phase shift. This results in a
minimum response time of approximately 100 ms (at 50 Hz).
The "df/dt (ROCOF)"
conguration parameters are located below the "SyA. decoupling"
function menu on the display.
ID Parameter CL Setting range
[Default]
Description
3104 Limit 2 0.1 to 9.9 Hz/s
[2.6 Hz/s]
(Hysteresis: 0.1 Hz/s)
(Reset Delay: 80 ms)
The df/dt threshold is dened here. If
this value is reached or exceeded for
at least the delay time without
interruption, an alarm with the class
congured in parameter
3101 is
initiated.
The decoupling procedure will open
the CBA.
3105 Delay 2 0.10 to 2.00 s
[0.10 s]
If the monitored rate of df/dt exceeds
the threshold value for the delay time
congured here, an alarm will be
issued.
If the monitored df/dt exceeds the
threshold (plus the hysteresis) again
102 LS-5 v2 Series 37650
4 Conguration
4.3 Congure Monitoring