ID Parameter CL Setting range
[Default]
Description
2850
2856
Monitoring
(Limit 1/Limit 2)
2 [On]
Overfrequency monitoring is carried
out according to the following
parameters. Monitoring is performed
at two levels. Both values may be
congured independent from each
other (prerequisite: Level 1 limit
< limit 2).
O Monitoring is disabled for Level 1 limit
and/or Level 2 limit.
2854
2860
Limit
(Limit 1/Limit 2)
2 100.0 to 130.0 %
2854: [100.4 %]
2860: [102.0 %]
The percentage values that are to be
monitored for each threshold limit are
dened here.
If this value is reached or exceeded
for at least the delay time without
interruption, the action specied by
the alarm class is initiated.
Notes
This value refers to the System rated
frequency (parameter 1750).
2855
2561
Delay
(Limit 1/Limit 2)
2 0.02 to 99.99 s
[0.06 s]
If the monitored system A frequency
value exceeds the threshold value for
the delay time congured here, an
alarm will be issued.
Notes
If the monitored frequency falls below
the threshold (minus the hysteresis)
before the delay expires the time will
be reset.
2851
2857
Alarm class
(Limit 1/Limit 2)
2 Class A/B/C/D/E/F/Control
2851: [A]
2857: [B]
Each limit may be assigned an
independent alarm class that species
what action should be taken when the
limit is surpassed.
Notes
For additional information refer to ╚═▷
“9.4.1 Alarm Classes”
2852
2858
Self acknowledge
(Limit 1/Limit 2)
2 Yes The control unit automatically clears
the alarm if the fault condition is no
longer detected.
[No] The control unit does not
automatically reset the alarm when
the fault condition is no longer
detected.
The alarm must be acknowledged and
reset by manually pressing the
104 LS-5 v2 Series 37650
4 Conguration
4.3 Congure Monitoring