[110 %] If the average voltage over 10
minutes is higher, the action specied
by the alarm class is initiated.
Notes
This value refers to the "SyA. rated
voltage" (parameter 1766).
8808 SyA. decoupling voltage increase 2 Yes Voltage increase monitoring does
cause decoupling.
[No] Voltage increase monitoring does not
cause decoupling.
8831 Alarm class 2 Class A/B/C/D/E/F/Control
[B]
Each limit may be assigned an
independent alarm class that species
what action should be taken when the
limit is surpassed.
Notes
For additional information refer to ╚═▷
“9.4.1 Alarm Classes”
8832 Self acknowledge 2 [Yes] The control unit automatically clears
the alarm if the fault condition is no
longer detected.
No The control unit does not
automatically reset the alarm when
the fault condition is no longer
detected.
The alarm must be acknowledged and
reset by manually pressing the
appropriate buttons or by activating
the LogicsManager output "External
acknowledgement" (via a discrete
input or via an interface).
8833 Monitoring lockable 2 Yes Monitoring for fault conditions is only
performed if "Lock Monitoring Status
24.40" is false
[No] Monitoring for this fault condition is
continuously enabled regardless of
"Lock Monitoring Status 24.40".
8849 AND characteristics 2 On If the 10 minute voltage averages of
all phases exceed the limit, the
monitoring is tripping.
[O] If the 10 minute voltage average of at
least one phase exceeds the limit,
the monitoring is tripping.
4.3.1.11 Setup System A for VDE-AR-N 4105
General notes
The German Grid Code VDE-AR-N 4105 instructs the handling of electrical energy sources
running parallel to the low voltage grid. This rule has an impact with some items on the
113LS-5 v2 Series37650
4 Conguration
4.3 Congure Monitoring