Fig. 75: QV monitoring - schematic
ID Parameter CL Setting range
[Default]
Description
3292 Monitoring 2 [On] QV monitoring is carried out according
to the following parameters.
O󰈠 No monitoring is carried out.
3285 Limit undervoltage 2 45 to 150 %
[85 %]
The percentage voltage value that is
to be monitored is de󰈡ned here.
If the voltages of all phases (one
phase in 1Ph 2W system) are below
this limit, the voltage condition for
tripping the monitoring function is
TRUE.
Notes
This value refers to the "SyA. rated
voltage" (parameter 1766).
3291 Reactive power threshold 2 2 to 100 %
[5 %]
The percentage reactive value that is
to be monitored is de󰈡ned here.
If the absolute value of reactive power
Q is higher than this threshold, the
120 LS-5 v2 Series 37650
4 Con󰈡guration
4.3 Con󰈡gure Monitoring
Released