EasyManua.ls Logo

Woodward LS-5 v2 Series - System B

Woodward LS-5 v2 Series
448 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ID Parameter CL Setting range
[Default]
Description
3970 Monitoring 2 [On] Phase rotation monitoring is carried
out according to the following
parameters.
O󰈠 No monitoring is carried out.
3974 SyA. phase rotation 2 [CW] The three-phase measured system A
voltage is rotating CW (clock-wise;
that means the voltage rotates in L1-
L2-L3 direction; standard setting).
CCW The three-phase measured system A
voltage is rotating CCW (counter
clock-wise; that means the voltage
rotates in L1-L3-L2 direction).
3971 Alarm class 2 Class A/B/C/D/E/F/Control
[B]
Each limit may be assigned an
independent alarm class that speci󰈡es
what action should be taken when the
limit is surpassed.
Notes
For additional information refer to ╚═▷
“9.4.1 Alarm Classes”
3972 Self acknowledge 2 Yes The control unit automatically clears
the alarm if the fault condition is no
longer detected.
[No] The control unit does not
automatically reset the alarm when
the fault condition is no longer
detected.
The alarm must be acknowledged and
reset by manually pressing the
appropriate buttons or by activating
the LogicsManager output "External
acknowledgement" (via a discrete
input or via an interface).
3973 Monitoring lockable 2 Yes Monitoring for fault conditions is only
performed if "Lock Monitoring Status
24.40" is false.
[No] Monitoring for this fault condition is
continuously enabled regardless of
"Lock Monitoring Status 24.40".
4.3.2
System B
ID Parameter CL Setting range
[Default]
Description
127LS-5 v2 Series37650
4 Con󰈡guration
4.3 Con󰈡gure Monitoring
Released

Table of Contents

Related product manuals