EasyManua.ls Logo

Woodward LS-5 v2 Series - CBA Unload Mismatch

Woodward LS-5 v2 Series
448 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3071 Alarm class 2 Class A/B/C/D/E/F/Control
[B]
Each limit may be assigned an
independent alarm class that speci󰈡es
what action should be taken when the
limit is surpassed.
Notes
For additional information refer to ╚═▷
“9.4.1 Alarm Classes”
3072 Self acknowledge 2 Yes The control unit automatically clears
the alarm if the fault condition is no
longer detected.
[No] The control unit does not
automatically reset the alarm when
the fault condition is no longer
detected.
The alarm must be acknowledged and
reset by manually pressing the
appropriate buttons or by activating
the LogicsManager output "External
acknowledgement" (via a discrete
input or via an interface).
3075 Monitoring lockable 2 Yes Monitoring for fault conditions is only
performed if "Lock Monitoring Status
24.40" is false.
[No] Monitoring for this fault condition is
continuously enabled regardless of
"Lock Monitoring Status 24.40".
4.3.3.3 CBA Unload Mismatch
ID Parameter CL Setting range
[Default]
Description
8819 Unload trip level CBA 2 0.5 to 99.9 %
[3.0 %]
If the monitored power of system A
falls below this value, a "CBA open"
command will be issued.
Notes
This value refers to the "SyA. rated
active power" (parameter 1752).
8835 Delay 2 1 to 999 s
[60 s]
If the monitored system A power does
not fall below the limit con󰈡gured in
parameter 8819 before the time
con󰈡gured here expires, a "CBA open"
command will be issued together with
an alarm "CBA unload mismatch" and
the logical command variable "08.36"
will be enabled.
8836 Alarm class 2 Class A/B/C/D/E/F/Control Each limit may be assigned an
independent alarm class that speci󰈡es
133LS-5 v2 Series37650
4 Con󰈡guration
4.3 Con󰈡gure Monitoring
Released

Table of Contents

Related product manuals