ID Parameter CL Setting range
[Default]
Description
2600 CBB monitoring 2 [On] Monitoring of the CBB is carried out
according to the following parameters.
O Monitoring is disabled.
2601 CBB alarm class 2 Class A/B
[B]
Each limit may be assigned an
independent alarm class that species
what action should be taken when the
limit is surpassed.
Notes
For additional information refer to ╚═▷
“9.4.1 Alarm Classes”
3418 CBB maximum attempts of closure 2 1 to 10
[5]
The maximum number of breaker
closing attempts is congured in this
parameter (relay output "Command:
close CBB").
When the breaker reaches the
congured number of attempts, a
"CBB fail to close" alarm is issued.
The counter for the closure attempts
will be reset as soon as the "Reply
CBB" is de-energized for at least
5 seconds to signal a closed CBB.
3420 CBB open monitoring 2 0.10 to 5.00 s
[2.00 s]
If the "Reply CBB" is not detected as
energized once this timer expires, a
"CBB fail to open" alarm is issued.
This timer initiates as soon as the
"open breaker" sequence begins. The
alarm congured in parameter 2601 is
issued.
2602 CBB monitoring lockable 2 Yes Monitoring for fault conditions is only
performed if "Lock Monitoring Status
24.40 is false".
[No] Monitoring for this fault condition is
continuously enabled regardless of
"Lock Monitoring Status 24.40".
4.3.3.5
Synchronization CBB
For synchronization with two systems please see additionally
╚═▷ “9.5.1 Synchronization
Of System A and System B”.