3060 Monitoring 2 [On] Monitoring of the CBB synchronization
is carried out according to the
following parameters.
O Monitoring is disabled.
3063 Delay 2 3 to 999 s
[60 s]
If it was not possible to synchronize
the CBB within the time congured
here, an alarm will be issued.
The message "CBB syn. timeout" is
issued and the logical command
variable "08.30" will be enabled.
3061 Alarm class 2 Class A/B/C/D/E/F/Control
[B]
Each limit may be assigned an
independent alarm class that species
what action should be taken when the
limit is surpassed.
Notes
For additional information refer to ╚═▷
“9.4.1 Alarm Classes”
3062 Self acknowledge 2 Yes The control unit automatically clears
the alarm if the fault condition is no
longer detected.
[No] The control unit does not
automatically reset the alarm when
the fault condition is no longer
detected.
The alarm must be acknowledged and
reset by manually pressing the
appropriate buttons or by activating
the LogicsManager output "External
acknowledgement" (via a discrete
input or via an interface).
3065 Monitoring lockable 2 Yes Monitoring for fault conditions is only
performed if "Lock Monitoring Status
24.40" is false.
[No] Monitoring for this fault condition is
continuously enabled regardless of
"Lock Monitoring Status 24.40".
4.3.3.6 CBB Unload Mismatch
ID Parameter CL Setting range
[Default]
Description
3125 Unload trip level CBB 2 0.5 to 99.9 %
[3.0 %]
If the monitored power ow of system
B falls below this value, a "CBB open"
command will be issued.
Notes
136 LS-5 v2 Series 37650
4 Conguration
4.3 Congure Monitoring