no trip occurs and the nal opening is completed
within longest 210ms.
4.3.4
Voltage plausibility
General notes
If there is a connection between System A and System B based on breaker feedbacks, the
monitoring function compares the status ags of System A (logical command variable
02.11) and System B (logical command variable 02.05) on same condition. Additionally, if
both systems are okay, the monitor expects to see a phase angle between both systems
less than +/- 10°. The intension of this monitor is to detect wiring failures or blown fuses.
An alarm will be initiated if
• the status ags of System A (02.11) and System B (02.05) do not have the same
condition
• the status ags of System A (02.11) and System B (02.05) have the same condition
but the phase angle between both systems is too big
If this protective function is triggered, the display indicates "Voltage mismatch" and the
logical command variable "08.47" will be enabled.
ID Parameter CL Setting range
[Default]
Description
2991 Monitoring 2 On Voltage plausibility monitoring is
carried out according to the following
parameters.
[O] Monitoring is disabled.
2995 Delay 2 1 to 999 s
[30 s]
If the monitored conditions are met for
the delay time congured here, an
alarm will be issued.
2992 Alarm class 2 Class A/B/C/D/E/F/Control
[B]
Each limit may be assigned an
independent alarm class that species
what action should be taken when the
limit is surpassed.
Notes
For additional information refer to ╚═▷
“9.4.1 Alarm Classes”
2993 Self acknowledge 2 Yes The control unit automatically clears
the alarm if the fault condition is no
longer detected.
[No] The control unit does not
automatically reset the alarm when
140 LS-5 v2 Series 37650
4 Conguration
4.3 Congure Monitoring