System A
System B
CBA
CBB
System A
System B
CBA
CBB
Close
Command
active
Close
Command
active
System A
System B
CBA
CBB
System A
System B
CBA
CBB
Close
Command
active
Close
Command
active
Connect
Open Load to A dead
Connect
Open Load to A alive
Connect
Open Load to B dead
Connect
Open Load to B alive
On/Off
Open
Load
Open
Load
Open
Load
Open
Load
On/OffOn/OffOn/Off
Fig. 77: Dead busbar: Open load segment closure
ID Parameter CL Setting range
[Default]
Description
9013 Connect open load to A dead 2 On The CBA closure of an open load onto
a dead busbar system A is enabled.
[O] The CBA closure of an open load onto
a dead busbar system A is disabled.
This parameter determines an open
load closure in a situation when
busbar system A is dead.
Notes
No access in application mode
A05
.
9014 Connect open load to A alive 2 [On] The CBA closure of an open load onto
an alive busbar system A is enabled.
O The CBA closure of an open load onto
an alive busbar system A is disabled.
This parameter determines an open
load closure in a situation when
busbar system A is alive.
Notes
No access in application mode
A05
.
9015 Connect open load to B dead 2 On The CBB closure of an open load onto
a dead busbar system B is enabled.
[O] The CBB closure of an open load onto
a dead busbar system B is disabled.
This parameter determines an open
load closure in a situation when
busbar system B is dead.
155LS-5 v2 Series37650
4 Conguration
4.4 Congure Application