enabled only after the open pulse is
issued.
[No] The CB close pulse is enabled without
being preceded by a CB open pulse.
5708 CBB open time pulse 2 0.10 to 9.90 s
[1.00 s]
This time denes the length of the
CBB open time pulse, if the automatic
switch unblocking CBB (parameter
3405) is activated.
8829 Open CBB in manual 2 [Immediate] If there is an open command in
manual mode, the CBB will open
immediately.
With unl. If there is an open command in
manual mode, the CBB will open with
unloading. If there is a further open
command while unloading (via LM or
button) the CBB opens immediately.
Notes
With the exception of application
mode
A01
, unloading is skipped, if no
closed GCB in the relevant segments
is detected.
No access in application mode
A05
.
12898 Open CBB in MAN 2 Determined by
LogicsManager
[(0&1)&1]
Once the conditions of the
LogicsManager have been fullled the
LS-5 opens the CBB immediately or
with unloading (according to
parameter 8829), if no other LS-5 with
higher priority likes to do the same.
Notes
If a close or open command is active
but is blocked by another device with
higher priority the display shows "CBB
request".
Only in operation mode MANUAL.
No access in application mode
A05
.
12899 Close CBB in MAN 2 Determined by
LogicsManager
[(0&1)&1]
Once the conditions of the
LogicsManager have been fullled the
LS-5 closes the CBB, if no other LS-5
with higher priority likes to do the
same. (Provided the conditions for
dead bus closure or synchronization
are true.)
Notes
If a close or open command is active
but is blocked by another device with
higher priority the display shows "CBB
request".
Only in operation mode MANUAL.
No access in application mode
A05
.
163LS-5 v2 Series37650