EasyManua.ls Logo

Woodward LS-5 v2 Series - Synchronization Configuration

Woodward LS-5 v2 Series
448 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.4.2.5 Synchronization Con󰆟guration
For synchronization with two systems please see additionally ╚═▷ “9.5.1 Synchronization
Of System A and System B.
Phase angle compensation
To determine the phase angle deviation (to be con󰈡gured with the parameters listed
below) do either of the following:
When mains voltage can be connected follow the steps in Procedure.
When mains voltage cannot be connected but the vector group of the transformer is
known, follow the steps in Procedure
Determining the phase angle deviation (connected mains voltage)
The mains voltage is connected:
1. ▷
With a phase angle deviation of 0 ° and system B not energized and system A
energized, close the CBA.
This will result in system A and system B being at the same voltage potential.
The phase angle deviation will now be displayed on the LS-5 screen (synchronization
angle phi).
2. ▷
Enter the displayed value into parameter 8824.
NOTICE!
Damaged components due to incorrect settings
Validate the setting in every control unit with a di󰈠erential voltage
measurement.
Calculating the phase angle deviation (known transformer vector group)
The vector group states the phase angle deviation in multiples of 30°. From the vector
group the phase angle deviation can be calculated as an angle between 0° and 360°:
1. ▷
To calculate the resulting value, assume the low voltage side of the
transformer always lags behind the high voltage side (phase angle deviation
α).
Calculate the phase angle deviation as follows:
High voltage side = System
[A]
High voltage side = System
[B]
α < 180° α
α > 180° -360° + α 360° -α
Tab. 17: Calculation of the phase angle deviation
167LS-5 v2 Series37650
4 Con󰈡guration
4.4 Con󰈡gure Application
Released

Table of Contents

Related product manuals