opposite the mains voltage of the
MCB. The opposite side of the CB is
therefore either constant (mains
voltage) or a controlled stable (bus
coupler) system.
System A Variable system is system A.
[System B] Variable system is system B.
By LM A LogicsManager equation determines
whether variable system is system A
or system B (parameter 12949).
Notes
No access in the application mode
A05
.
12949 Variab. system A
(Variable system A )
2 Determined by
LogicsManager
[(0 & 1) & 1]
Once the conditions of the
LogicsManager have been ful󰈡lled the
system A will be the variable one.
If the conditions of the LogicsManager
have not been ful󰈡lled the system B
will be the variable one.
This con󰈡guration is only valid, if the
variable system is con󰈡gured as 'By
LM'.
Notes
No access in the application mode
A05
.
For information on the LogicsManager
and its default settings see ╚═▷ “9.3.1
LogicsManager Overview”.
4.4.4
Automatic Run
Priority of operation modes
The priority of operation modes is well de󰈡ned from highest to lowest priority:
“MANUAL” is higher than
AUTOMATIC
ID Parameter CL Setting range
[Default]
Description
8827 Startup in mode
(Operating mode after applying the
power supply )
2 If the controller is powered down, the
unit will start in the following
con󰈡gured mode when it is powered
up again.
[AUTO] The unit starts in the AUTOMATIC
operating mode.
180 LS-5 v2 Series 37650
4 Con󰈡guration
4.4 Con󰈡gure Application
Released