The hide and unhide of parameters of discrete outputs is handled di󰈠erently by HMI and
ToolKit.
ID Parameter CL Setting range
[Default]
Description
12580 Ready for op. O󰆞
(Ready for operation OFF)
2 Determined by
LogicsManager
The "Ready for operation OFF" relay is
energized by default if the power
supply exceeds 8 V.
Once the conditions of the
LogicsManager have been ful󰈡lled, the
relay will be de-energized. This
LogicsManager output may be
con󰈡gured with additional conditions,
which may signal a PLC an "out of
operation" condition by de-energizing
the relay on terminals 30/31, like
"shutdown alarm" or no "AUTO mode"
present.
Notes
For information on the LogicsManager
and its default settings see ╚═▷ “9.3.1
LogicsManager Overview”.
12110 Relay {x} 2 Determined by
LogicsManager
Once the conditions of the
LogicsManager have been ful󰈡lled, the
relay will be energized.
Notes
For information on the LogicsManager
and its default settings see ╚═▷ “9.3.1
LogicsManager Overview”.
Parameter IDs
The parameter ID above refers to relay 2.
Refer to ╚═▷ Tab. 20 for the parameter IDs of the parameters for relay 3 to relay 6.
R 1 R 2 R 3 R 4 R 5 R 6
Parameter ID 12580 12110 12310 12320 12130 12140
Tab. 20: Discrete outputs - relay parameter IDs