4.6 Con󰆟gure Interfaces
4.6.1
General
ID Parameter CL Setting range
[Default]
Description
8051 ToolKit interface 2 [Serial 1] ToolKit is working at Serial #1
interface (RS-232)
Notes
This is the preferred ToolKit
connection via Service port (RJ45
connector).
See ╚═▷ “4.6.3 RS-232 Interface” for
details.
Serial 2 ToolKit is working at Serial #2
interface (RS-485)
4.6.2
CAN Interface
General notes
The CAN bus is a
󰈡eld bus and subject to various disturbances. Therefore, it cannot be
guaranteed that every request will be answered. We recommend to repeat a request,
which is not answered within reasonable time.
ID Parameter CL Setting range
[Default]
Description
9923 Comm. LS5 <-> gen. device 2 The interface, which is used for
transmitting the LS-5 data and
easYgen load share data is con󰈡gured
here.
[CAN #1] Use CAN interface 1.
O󰈠 Deactivate interface.
9921 Transfer rate fast message 2 0.10 to 0.30 s
[0.10 s]
The transfer rate de󰈡nes the time
delay between two fast CAN
messages.
Notes
In case of CAN systems with a high
bus load (e.g. long distance between
the units with low baud rate), a
shorter transfer rate (higher time
setting) helps to reduce the bus load.
192 LS-5 v2 Series 37650
4 Con󰈡guration
4.6 Con󰈡gure Interfaces
Released