If this parameter is congured to
"O", the Master controller (for
example a PLC) must send a
"Start_Remote_node" message to
initiate the load share message
transmission of the easYgen.
If no "Start_Remote_node" message
would be sent, the complete system
would not be operational.
9120 Producer heartbeat time 2 0 to 65500 ms
[2000 ms]
Independent from the CANopen
Master conguration, the unit
transmits a heartbeat message with
this congured heartbeat cycle time.
If the producer heartbeat time is equal
0, the heartbeat will only be sent as
response to a remote frame request.
The time congured here will be
rounded up to the next 20 ms step.
9100 COB-ID SYNC Message 2 1 to FFFFFFFF hex
[80 hex]
This parameter denes whether the
unit generates the SYNC message or
not.
The message complies with CANopen
specication: object 1005; subindex 0
denes the COB-ID of the
synchronization object (SYNC).
Notes
The structure of this object is shown in
╚═▷ “COB-ID messages”.
8940 Producer SYNC Message time 2 0 to 65000 ms
[20 ms]
This is the cycle time of the SYNC
message. If the unit is congured for
this function (parameter 9100) it will
send the SYNC message with this
interval. The time congured here will
be rounded up to the next 10 ms step.
9101 COB-ID TIME Message 2 1 to FFFFFFFF hex
[100 hex]
This parameter denes whether the
unit generates the TIME message or
not.
Complies with CANopen specication:
object 1012, subindex 0; denes the
COB-ID of the time object (TIME).
Notes
The structure of this object is shown in
╚═▷ “COB-ID messages”.