3163 Baudrate 2 2.4 / 4.8 / 9.6 / 14.4 /
[19.2] / 38.4 / 56 / 115
kBaud
This parameter de󰈡nes the baud rate
for communications. Please note, that
all participants on the bus must use
the same baud rate.
3161 Parity 2 [No] / Even / Odd The used parity of the interface is set
here.
3162 Stop bits 2 [One] / Two The number of stop bits is set here.
3185 ModBus Slave ID 2 0 to 255
[33]
The Modbus device address, which is
used to identify the device via
Modbus, is entered here.
If "0" is con󰈡gured here, the Modbus
is disabled.
3186 Reply delay time 2 0.00 to 1.00 s
[0.00 s]
This is the minimum delay time
between a request from the Modbus
master and the sent response of the
slave.
This time is also required if an
external interface converter to RS-485
is used for example.
4.6.4
RS-485 Interface
ID Parameter CL Setting range
[Default]
Description
3170 Baudrate 2 2.4 / 4.8 / 9.6 / 14.4 /
[19.2] / 38.4 / 56 / 115
kBaud
This parameter de󰈡nes the baud rate
for communications. Please note, that
all participants on the bus must use
the same baud rate.
3171 Parity 2 [No] / Even / Odd The used parity of the interface is set
here.
3172 Stop bits 2 [One] / Two The number of stop bits is set here.
3188 ModBus Slave ID 2 0 to 255
[33]
The Modbus device address, which is
used to identify the device via
Modbus, is entered here.
If "0" is con󰈡gured here, the Modbus
is disabled.
3189 Reply delay time 2 0.00 to 2.55 s
[0.00 s]
This is the minimum delay time
between a request from the Modbus
master and the sent response of the
203LS-5 v2 Series37650