slave. This time is required in half-
duplex mode.
4.6.5
Modbus Protocol (5300 Multiple)
ID Parameter CL Setting range
[Default]
Description
3181 Power [W] exponent 10^x 2 2 to 5
[3]
This setting adjusts the format of the
16 bit power values in the data
telegram.
Notes
For an example refer to ╚═▷ “Power
measurement example”.
3182 Voltage [V] exponent 10^x 2 -1 to 2
[0]
This setting adjusts the format of the
16 bit voltage values in the data
telegram.
Notes
For an example refer to ╚═▷ “Voltage
measurement example”.
3183 Current [A] exponent 10^x 2 -1 to 0
[0]
This setting adjusts the format of the
16 bit current values in the data
telegram.
Notes
For an example refer to ╚═▷ “Current
measurement example”.
Power measurement example
Refer to parameter
3181.
• The measurement range is 0…250 kW
•
Momentarily measurement value = 198.5 kW (198.500 W)
Setting Meaning Calculation Transfer value
(16Bit, max.
32767)
Possible display
format
2
10
2
198500 W / 10
2
1985 198.5 kW
3
10
3
198500 W / 10
3
198 198 kW
4
10
4
198500 W / 10
4
19 N/A