Setting Meaning Calculation Transfer value
(16Bit, max.
32767)
Possible display
format
5
10
5
198500 W / 10
5
1 N/A
Voltage measurement example
Refer to parameter
3182.
The measurement range is 0…480 V
Momentarily measurement value = 477.8 V
Setting Meaning Calculation Transfer value
(16Bit, max.
32767)
Possible display
format
-1
10
-1
477.8 V / 10
-1
4778 47.8 V
0
10
0
477.8 V / 10
0
477 477 V
1
10
1
477.8 V / 10
1
47 N/A
2
10
2
477.8 V / 10
2
4 N/A
Current measurement example
Refer to parameter
3183.
The measurement range is 0…500 A
Momentarily measurement value = 345.4 A
Setting Meaning Calculation Transfer value
(16Bit, max.
32767)
Possible display
format
-1
10
-1
345.4 A / 10
-1
3454 345.4 A
0
10
0
345.4 A / 10
0
345 345 A
4.7 Con󰆟gure LogicsManager
Logical symbols
The LS-5 LogicsManager screens show logical symbols according to the IEC standard.
205LS-5 v2 Series37650
4 Con󰈡guration
4.7 Con󰈡gure LogicsManager