ID Parameter CL Setting range
[Default]
Description
1676 Sunday active 2 Yes The switch point is enabled every
Sunday.
[No] The switch point is disabled every
Sunday.
4.8 Congure Counters
ID Parameter CL Setting range
[Default]
Description
2515 Counter value preset 2 0 to 999,999.99
[0]
This value is utilized to set the
following counters:
• MWh counter
• Mvarh counter
The number entered into this
parameter is the number that will be
set to the parameters listed below
when they are enabled.
2510 Set SyA. active energy [0.00 MWh] 2 Yes The current value of this counter is
overwritten with the value congured
in "Counter value preset" (parameter
2515). After the counter has been
(re)set, this parameter changes back
to "No" automatically.
[No] The value of this counter is not
changed.
Example
• The counter value preset
(parameter 2515) is congured
to "3456".
•
If this parameter is set to "Yes",
the "System A active power"
counter will be set to 34.56 MWh.
2512 Set SyA. -active energy [0.00
MWh]
2 Yes The current value of this counter is
overwritten with the value congured
in "Counter value preset" (parameter
2515). After the counter has been
(re)set, this parameter changes back
to "No" automatically.
[No] The value of this counter is not
changed.
Example
• The counter value preset
(parameter 2515) is congured
to "3456".
211LS-5 v2 Series37650
4 Conguration
4.8 Congure Counters