Displayed value Press Symbol
(lower
left)
Monitoring Displayed at parameter setting
3Ph4W 3Ph4WOD 3Ph3W 1Ph2W 1Ph3W
System B
frequency
System B voltage and system B frequency are
identical to page one
Load power — Sum of active power system A and system B
Notes
For details of calculating the load power please refer
to ╚═▷ “3.3.6 Power Measuring”.
Tab. 30: Measuring values page two
5.2.3.2 Alarm List
Fig. 111: Alarm List screen (example)
All alarm messages, which have not been acknowledged and cleared, are displayed. Each
alarm is displayed with the alarm message and the date and time of the alarm occurred
in the format mon-dd hh:mm:ss.ss.
Self-acknowledging alarm messages get a new timestamp when initializing the unit
(switching on).
A maximum of 16 alarm messages can be displayed. If 16 alarm messages are already
displayed and further alarm messages occur, these will not be displayed before displayed
alarm messages are acknowledged and thus deleted from the list.
Symbol/Button Description
Indicates that corresponding alarm condition is still present.
Acknowledge the selected alarm message (displayed inverted).
Acknowledgment is only possible, if the alarm condition is no longer present. If the Alarm
LED is still ashing (an alarm is present, which has not yet been acknowledged as
'Seen'), this softkey resets the horn and acknowledges the alarm as 'Seen'.
241LS-5 v2 Series37650
5 Operation
5.2 Front Panel Access