LS-512/LS-522 easYgen-3400/3500 or
easYgen-3400XT/
3500XT
Mode Symbol Mode Symbol Function
Mains decoupling function in the LS-5 con󰈡gurable, for LS-5
connected with system A at mains.
Handling of CBB (dead bus closure, synchronization, open)
initiated by the corresponding command variables or by
manual commands.
Measuring of active and reactive power on system B.
Calculating of an active and reactive load.
L-GGBMCB
A05
GCB/L-
GGBMCB
A12
LS-5 as GGB and MCB control in combination with
easYgen-3400/3500 or easYgen-3400XT/3500XT in a 󰈡xed
application. Only one LS-5x2 is allowed.
This application mode provides the following functions:
Handling of a GGB (dead bus closure, synchronization, open)
initiated by the easYgen.
Handling of a MCB (dead bus closure, synchronization, open)
initiated by the easYgen.
Measuring and monitoring of system A values, (mains voltage,
mains frequency, mains phase rotation, mains current),
transferred to easYgen.
Measuring of system B values, (voltage, frequency, phase
rotation), transferred to easYgen.
Measuring of mains active and mains reactive power on
system A.
Automatic con󰈡guration of the relevant parameters.
Mains decoupling function in the LS-5 con󰈡gurable.
Measuring of active and reactive power 󰈢ow on system B.
Calculating of an active and reactive load.
6.1.2.2 easYgen-3400/3500 or easYgen-3400XT/3500XT View
easYgen-3400/3500 or
easYgen-3400XT/
3500XT
LS-512/LS-522
Mode Symbol Mode Symbol Function
GCB/LS5
A07
LS5
A02
One or more easYgen in combination with an open LS-5 system,
individually con󰈡gurable for di󰈠erent application. Multiple isolated
and/or mains parallel operation. Multiple LS-5x1 and LS-5x2 are
allowed (max. 16 LS-5xx).
This application mode provides the following functions:
Handling of the GCB (dead bus closure, synchronization, open)
initiated by start command in AUTO or individually in MAN
mode.
Measuring and monitoring of generator values (voltage,
frequency, phase rotation, current and power).
Measuring of generator busbar values (voltage, frequency).
Indicating of mains values (voltage, frequency) sent from
'Mains'-LS-5 with the smallest ID in the own segment.
Indicating the sum of active and reactive power sent from all
'Mains'-LS-5 in the own segment.
Regulating Import/Export power with the sum of active and
reactive power sent from all 'Mains'-LS-5 in the own segment.
258 LS-5 v2 Series 37650
6 Application
6.1 Application Modes Overview