LS-512/LS-522 easYgen-3400/3500 or
easYgen-3400XT/
3500XT
Mode Symbol Mode Symbol Function
• Mains decoupling function in the LS-5 congurable, for LS-5
connected with system A at mains.
• Handling of CBB (dead bus closure, synchronization, open)
initiated by the corresponding command variables or by
manual commands.
• Measuring of active and reactive power on system B.
•
Calculating of an active and reactive load.
L-GGBMCB
A05
GCB/L-
GGBMCB
A12
LS-5 as GGB and MCB control in combination with
easYgen-3400/3500 or easYgen-3400XT/3500XT in a xed
application. Only one LS-5x2 is allowed.
This application mode provides the following functions:
• Handling of a GGB (dead bus closure, synchronization, open)
initiated by the easYgen.
•
Handling of a MCB (dead bus closure, synchronization, open)
initiated by the easYgen.
•
Measuring and monitoring of system A values, (mains voltage,
mains frequency, mains phase rotation, mains current),
transferred to easYgen.
•
Measuring of system B values, (voltage, frequency, phase
rotation), transferred to easYgen.
• Measuring of mains active and mains reactive power on
system A.
• Automatic conguration of the relevant parameters.
•
Mains decoupling function in the LS-5 congurable.
• Measuring of active and reactive power ow on system B.
• Calculating of an active and reactive load.
6.1.2.2 easYgen-3400/3500 or easYgen-3400XT/3500XT View
easYgen-3400/3500 or
easYgen-3400XT/
3500XT
LS-512/LS-522
Mode Symbol Mode Symbol Function
GCB/LS5
A07
LS5
A02
One or more easYgen in combination with an open LS-5 system,
individually congurable for dierent application. Multiple isolated
and/or mains parallel operation. Multiple LS-5x1 and LS-5x2 are
allowed (max. 16 LS-5xx).
This application mode provides the following functions:
• Handling of the GCB (dead bus closure, synchronization, open)
initiated by start command in AUTO or individually in MAN
mode.
•
Measuring and monitoring of generator values (voltage,
frequency, phase rotation, current and power).
• Measuring of generator busbar values (voltage, frequency).
•
Indicating of mains values (voltage, frequency) sent from
'Mains'-LS-5 with the smallest ID in the own segment.
• Indicating the sum of active and reactive power sent from all
'Mains'-LS-5 in the own segment.
• Regulating Import/Export power with the sum of active and
reactive power sent from all 'Mains'-LS-5 in the own segment.
258 LS-5 v2 Series 37650
6 Application
6.1 Application Modes Overview