easYgen-3400/3500 or
easYgen-3400XT/
3500XT
LS-512/LS-522
Mode Symbol Mode Symbol Function
The easYgen recognizes through the LS-5 system the active
segment number.
Connection to mains (MCB is closed) is recognized via the LS-5
system, if one or more “Mains”-LS-5 are available.
The close and open commands for the single LS-5 breakers are
usually not generated in the easYgen.
Mains voltage and current is usually not connected at the
easYgen.
Exception: VDE-AR-N 4105 (refer to chapter VDE-AR-N 4105
╚═▷ “6.5 Setup VDE-AR-N 4105 Applications”)
Run-up synchronization, acting on the GCB, is possible.
GCB/L-
GGBMCB
A12
L-GGBMCB
A05
One or more easYgen with one LS-5x2 unit, acting on the GGB and
on the MCB in a 󰈡xed application. Multiple isolated and/or mains
parallel operation. The same handling as in the GCB/GGB/MCB
mode, but the GGB and MCB are operated by one LS-5x2.
This application mode provides the following functions:
Handling of the GCB (dead bus closure, synchronization, open)
initiated by start command in AUTO or individually in MAN
mode.
Handling of the GGB (dead bus closure, synchronization, open)
initiated by start command in AUTO or individually in MAN
mode according to the rule of the GCB/GGB/MCB mode.
Handling of the MCB (dead bus closure, synchronization, open)
in AUTO and MANUAL according to the rules of the
GCB/GGB/MCB mode.
Measuring and monitoring of generator values (voltage,
frequency, phase rotation, current and power).
Measuring of generator busbar values (voltage, frequency)
Indicating of mains values (voltage, frequency, phase angle)
sent from the LS-5x2.
Indicating of active and reactive power at the interchange
point sent from LS-5x2.
Regulating Import/Export power with active and reactive power
sent from LS-5x2.
Run-up synchronization, acting on the GCB or GCB/GGB, is
possible.
6.2
Setup Stand-Alone Applications (Mode A01)
Overview
The LS-5, con󰈡gured to application mode
A01
('Single LS-5'), runs as an independent unit
and does not expect any other unit on the CAN bus.
The idea of this mode is to use the LS-5x2 as a simple change over control (ATS)
controlled by discrete inputs or to run it together with a PLC. The PLC receives all
measurement values (voltages, current, power, phase angle) via communication interface
to run closed loop synchronization. Each breaker can be individually opened and closed,
whereby the LS-5 recognizes to “close only” or to synchronize.
259LS-5 v2 Series37650