Additionally the LS-5 can be used as a measurement transformer for displaying and
monitoring values. The decoupling functions (voltage, frequency, change of frequency)
can also be used when a parallel mains setup exists.
CBA Control
Current (3Ph)
Voltage (3Ph)
LS-5x2
Voltage (3Ph)
System A
System B
A01
PLC
Modbus
CAN bus
or
Current (1Ph)
CBB Control
Load
Fig. 142: Application mode
A01
General notes
NOTICE!
Dead bus interlocking due to incorrect setup
No other LS-5 or easYgen device is expected on the CAN bus. After power-up the LS-5
can carry out a dead bus closure regardless if other devices are connected to the bus
(arbitration time is ignored).
Nevertheless, dead bus interlocking occurs, if the LS-5 detects another device (with
higher priority) within 40 seconds after power-up on the CAN bus, which wants to carry
out a dead bus closure.
The LS-5 acts as if there is no other LS-5 in the system.
Prerequisites
Personnel:
Quali󰈡ed electrician
1. ▷
For a mains decoupling function, connect the system A measurement on the mains
busbar.
2. ▷
Setup the PLC to act as master and to monitor the functionality of the communication
interface.
Con󰆟gure LS-5
260 LS-5 v2 Series 37650
6 Application
6.2 Setup Stand-Alone Applications (Mode A01)