No. Name Function
28.03 Command 3 to LS5 easYgen (OR) Open and close GGB
28.04 Command 4 to LS5 easYgen (OR)
28.05 Command 5 to LS5 easYgen (OR) Handling open or closed transition
28.06 Command 6 to LS5 easYgen (OR)
The manual control of the GCB, GGB and MCB is restricted to the easYgen(s). In the
LS-5x2 there is no Manual mode available.
LS-5x2
System A
System B
A05
CAN bus
MCB Control
Current (3Ph)
Voltage (3Ph)
Voltage (3Ph)
GGB Control
Current (1Ph)
LOAD
Dis./Analog Inputs
GCB Control
Current (3Ph)
MPU/ECU
Voltage (3Ph)
Engine Start/Stop
Voltage (1Ph)
A12
easYgen-3000
Dis./Analog Inputs
GCB Control
Current (3Ph)
MPU/ECU
Voltage (3Ph)
Engine Start/Stop
Voltage (1Ph)
A12
easYgen-3000
Dis./Analog Inputs
GCB Control
Current (3Ph)
MPU/ECU
Voltage (3Ph)
Engine Start/Stop
Voltage (1Ph)
A12
easYgen-3000
10
11
12
Segment
No.
Segment
No.
Segment
No.
Fig. 143: Application mode
A05
(example)
General notes
The LS-5x2 expects at least one easYgen device in the system.
The L-GGBMCB mode does not allow any other segmenting as demonstrated in the
drawing above. If further segments are desired, the easYgen and the LS-5 must be
congured to the free LS-5 mode: easYgen
A07
and LS-5
A02
.
263LS-5 v2 Series37650
6 Application
6.3 Setup easYgen & Slave LS-5x2 Applications (Mode A05)