Discrete outputs
Discrete outputs Potential free
Contact material AgCdO
General purpose (GP) (V
cont, relays
) AC 2.00 Aac@250 Vac
DC 2.00 Adc@24 Vdc
0.36 Adc@125 Vdc
Not suitable for USA and Canada
applications. Not evaluated by UL.
0.18 Adc@250 Vdc
Not suitable for USA and Canada
applications. Not evaluated by UL.
Pilot duty (PD) (V
cont, relays
) AC B300
DC 1.00 Adc@24 Vdc
Not suitable for USA and Canada
applications. Not evaluated by UL.
0.22 Adc@125 Vdc
Not suitable for USA and Canada
applications. Not evaluated by UL.
0.10 Adc@250 Vdc
Not suitable for USA and Canada
applications. Not evaluated by UL.
Analog input 0/4 to 20 mA (Active Power System A or B)
Analog input Alternative power measurement instead of
the system A or B power measurement by
CTs
Related to power
measurement
resolution
Resolution 11 Bit
0/4 to 20 mA input Internal load 50 Ω
Accuracy Class 1 ≤1% of full scale
8.1.4
Interface
Service Port interface (RS232/USB)
Service Port interface Not isolated
Proprietary interface Connect only with Woodward DPC cable
RS-485 interface
RS-485 interface Galvanically isolated
Insulation voltage (continuously) 100 Vac
Insulation test voltage (≤ 5 s) 1000 Vac
307LS-5 v2 Series37650
8 Technical Speci󰈡cations