Frequency range - random 10 Hz to 500 Hz
Power intensity 0.015 G²/Hz
RMS value 1.04 Grms
Standards MIL-STD 810F, M514.5A, Cat.4,
Truck/Trailer tracked-restrained
Cargo, Fig. 514.5-C1
Shock
Shock 40 G, Saw tooth pulse, 11 ms
Standards EN 60255-21-2
MIL-STD 810F, M516.5, Procedure 1
Temperature
Cold, Dry Heat (storage) -30 °C (-22 °F) / 80 °C (176 °F)
Cold, Dry Heat (operating) -20 °C (-4 °F) / 70 °C (158 °F)
Standards IEC 60068-2-2, Test Bb and Bd
IEC 60068-2-1, Test Ab and Ad
MILSTD -810D, M501.2 Induced, M502.2 Cold
LR Dry Heat, Cold, Envt 2,4, DNV Dry heat, Cold Class
A,C
Humidity
Humidity 95%, non condensing
Standards MIL-STD 810D, M507.2, PII
Marine environmental categories
Marine environmental categories Lloyd’s Register of Shipping (LRS):
ENV1, ENV2, ENV3 and ENV4
8.3 Accuracy
Measuring value Display Accuracy Measuring start Notes
Frequency
System A 40.0 to 85.0 Hz 0.1 % (of 85 Hz) 5 % (of PT secondary
voltage setting)
1
System B
Voltage
Wye system A / system
A
0 to 650 kV
1 % (of 120/480 V)
2
1.5 % (of PT secondary
voltage setting)
1
310 LS-5 v2 Series 37650
8 Technical Speci󰈡cations
8.3 Accuracy
Released