CAN Para-
meter
ID
Description Multiplier Units Model
Data
byte 0
(Mux)
Data
byte
2 1,2 144 System A frequency 0.01 Hz LS-5x1 v2,
LS-5x2 v2
2 3,4,5,6 171 System A average delta voltage 0.1 V LS-5x1 v2,
LS-5x2 v2
3 1,2 10202 Operation modes
13280 = CB A request
13264 = Unloading CB A
13210 = CB A Dead bus closure
13260 = Synchronization CB A
13205 = Mains settling time running
13257 = Open CB A
13279 = Synchronization network close CB A
13265 = Synchronization PERMISSIVE
13266 = Synchronization CHECK
13267 = Synchronization OFF
13286 = Synchronization segments close CB A
The following operation modes are supported
by the LS-5x2 v2 only:
13256 = Unloading CB B
13261 = CB B - CB A delay
13262 = CB A - CB B delay
13259 = Synchronization CB B
13255 = Open CB B
13340 = CB B request
13209 = CB B Dead bus closure
LS-5x1 v2,
LS-5x2 v2
3 3,4,5,6 337 System A total active power AC measurement 1 W LS-5x1 v2,
LS-5x2 v2
4 1,2 10107 Discrete outputs 1 to 6
Relay-Output 1 (inverted) Mask: 8000h Bit LS-5x1 v2,
LS-5x2 v2
Relay-Output 2 Mask: 4000h Bit LS-5x1 v2,
LS-5x2 v2
Relay-Output 3 Mask: 2000h Bit LS-5x1 v2,
LS-5x2 v2
Relay-Output 4 Mask: 1000h Bit LS-5x1 v2,
LS-5x2 v2
Relay-Output 5 Mask: 0800h Bit LS-5x1 v2,
LS-5x2 v2
Relay-Output 6 Mask: 0400h Bit LS-5x1 v2,
LS-5x2 v2
316 LS-5 v2 Series 37650
9 Appendix
9.2 Data Protocols