Loading...
CAN Para-
meter
ID
Description Multiplier Units Model
Data
byte 0
(Mux)
Data
byte
internal Mask: 0004h Bit
internal Mask: 0002h Bit
internal Mask: 0001h Bit
9.2.1.2
Data Protocol 5302 (Basic Visualization)
CAN Para-
meter
ID
Description Multiplier Units Model
Data
byte 0
(Mux)
Data
byte
0 1,2 Protocol ID, always 5302 LS-5x1 v2,
LS-5x2 v2
0 3,4,5,6 136 System A total reactive power 1 Var LS-5x1 v2,
LS-5x2 v2
1 1,2 160 System A power factor (cos.phi) 0.001 LS-5x1 v2,
LS-5x2 v2
1 3,4,5,6 170 System A average wye voltage 0.1 V LS-5x1 v2,
LS-5x2 v2
2 1,2 144 System A frequency 0.01 Hz LS-5x1 v2,
LS-5x2 v2
2 3,4,5,6 171 System A average delta voltage 0.1 V LS-5x1 v2,
LS-5x2 v2
3 1,2 10202 Operation modes
13280 = CB A request
13264 = Unloading CB A
13210 = CB A Dead bus closure
13260 = Synchronization CB A
13205 = Mains settling time running
13257 = Open CB A
13279 = Synchronization network close CB A
13265 = Synchronization PERMISSIVE
13266 = Synchronization CHECK
13267 = Synchronization OFF
13286 = Synchronization segments close CB A
The following operation modes are supported
by the LS-5x2 v2 only:
13256 = Unloading CB B
13261 = CB B - CB A delay
13262 = CB A - CB B delay
13259 = Synchronization CB B
LS-5x1 v2,
LS-5x2 v2
333LS-5 v2 Series37650