EasyManua.ls Logo

Woodward LS-5 v2 Series - Page 349

Woodward LS-5 v2 Series
448 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CAN Para-
meter
ID
Description Multiplier Units Model
Data
byte 0
(Mux)
Data
byte
07.08 System A underfrequency threshold 1 Mask: 2000h Bit LS-5x1 v2,
LS-5x2 v2
07.09 System A underfrequency threshold 2 Mask: 1000h Bit LS-5x1 v2,
LS-5x2 v2
07.10 System A overvoltage threshold 1 Mask: 0800h Bit LS-5x1 v2,
LS-5x2 v2
07.11 System A overvoltage threshold 2 Mask: 0400h Bit LS-5x1 v2,
LS-5x2 v2
07.12 System A undervoltage threshold 1 Mask: 0200h Bit LS-5x1 v2,
LS-5x2 v2
07.13 System A undervoltage threshold 2 Mask: 0100h Bit LS-5x1 v2,
LS-5x2 v2
07.14 System A phase shift Mask: 0080h Bit LS-5x1 v2,
LS-5x2 v2
07.25 System A decoupling Mask: 0040h Bit LS-5x1 v2,
LS-5x2 v2
internal Mask: 0020h Bit
internal Mask: 0010h Bit
07.26 System A voltage asymmetry (with
negative sequence)
Mask: 0008h Bit LS-5x1 v2,
LS-5x2 v2
07.05 System A phase rotation Mask: 0004h Bit LS-5x1 v2,
LS-5x2 v2
internal Mask: 0002h Bit
internal Mask: 0001h Bit
29 3,4,5,6 135 System A total active power 1 W LS-5x1 v2,
LS-5x2 v2
30 1,2 4138 internal Mask: 8000h Bit
internal Mask: 4000h Bit
internal Mask: 2000h Bit
internal Mask: 1000h Bit
internal Mask: 0800h Bit
internal Mask: 0400h Bit
internal Mask: 0200h Bit
internal Mask: 0100h Bit
07.15 df/dt (ROCOF) Mask: 0080h Bit LS-5x1 v2,
LS-5x2 v2
internal Mask: 0040h Bit
07.28 System A time-dependent voltage Mask: 0020h Bit LS-5x1 v2,
LS-5x2 v2
internal Mask: 0010h Bit
07.27 System A voltage increase Mask: 0008h Bit LS-5x1 v2,
LS-5x2 v2
349LS-5 v2 Series37650
9 Appendix
9.2 Data Protocols
Released

Table of Contents

Related product manuals