9.2.3
Additional Data Identier
9.2.3.1 Transmit Data
Remote control word 3
Object 21F9h (Parameter 505)
This object is required for remote control. These remote control bits can be used by a PLC
to send control signals via SDO or PDO, which can then be used as command variables in
the LogicsManager to control the easYgen. The data type is UNSIGNED16.
Bit 15 = 1 (ID 541) Remote control bit 16 (command variable 04.59)
Bit 14 = 1 (ID 542) Remote control bit 15 (command variable 04.58)
Bit 13 = 1 (ID 543) Remote control bit 14 (command variable 04.57)
Bit 12 = 1 (ID 544) Remote control bit 13 (command variable 04.56)
Bit 11 = 1 (ID 545) Remote control bit 12 (command variable 04.55)
Bit 10 = 1 (ID 546) Remote control bit 11 (command variable 04.54)
Bit 9 = 1 (ID 547) Remote control bit 10 (command variable 04.53)
Bit 8 = 1 (ID 548) Remote control bit 9 (command variable 04.52)
Bit 7 = 1 (ID 549) Remote control bit 8 (command variable 04.51)
Bit 6 = 1 (ID 550) Remote control bit 7 (command variable 04.50)
Bit 5 = 1 (ID 551) Remote control bit 6 (command variable 04.49)
Bit 4 = 1 (ID 552) Remote control bit 5 (command variable 04.48)
Bit 3 = 1 (ID 553) Remote control bit 4 (command variable 04.47)
Bit 2 = 1 (ID 554) Remote control bit 3 (command variable 04.46)
Bit 1 = 1 (ID 555) Remote control bit 2 (command variable 04.45)
Bit 0 = 1 (ID 556) Remote control bit 1 (command variable 04.44)
9.3
LogicsManager Reference
9.3.1
LogicsManager Overview
The LogicsManager is used to customize the sequence of events in the control unit such
as the start command of the engine or the operation of control unit relay outputs. For
example, the start routine may be programmed so that it requires the closing of a
discrete input or a preset time of day.
Depending on the application mode of the unit, the number of available relays that may
be programmed with the LogicsManager will vary.
Two independent time delays are provided for the congured action to take place and be
reset.
399LS-5 v2 Series37650
9 Appendix
9.3 LogicsManager Reference