No. Name Function Note
02.03 SyB. voltage ok SyB. voltage within operating
range
TRUE as long as the SyB. voltage
is within the operating range
02.04 SyB. freq. ok SyB. frequency within operating
range
TRUE as long as the SyB.
frequency is within the operating
range
02.05 SyB. volt./ freq. ok SyB. voltage and frequency within
operating ranges
TRUE as long as the SyB. voltage
and frequency are within the
operating ranges (02.03. and
02.04 are TRUE)
02.09 SyA. voltage ok SyA. voltage within operating
range
TRUE as long as the SyA. voltage
is within the operating range
02.10 SyA. freq. ok SyA. frequency within operating
range
TRUE as long as the SyA.
frequency is within the operating
range
02.11 SyA. volt. / freq. ok SyA. voltage and frequency within
operating ranges
TRUE as long as the SyA. voltage
and frequency are within the
operating ranges (02.09. and
02.10 are TRUE)
02.12 SyA. rot. CCW SyA. voltage: rotating direction
CCW
TRUE as long as the respective
rotation 󰈡eld is detected in case
of a three-phase voltage
measurement at the respective
measuring location
02.13 SyA. rot. CW SyA. voltage: rotating direction
CW
02.14 SyB. rot. CCW SyB. voltage: rotating direction
CCW
02.15 SyB. rot. CW SyB. voltage: rotating direction
CW
02.23 System A is dead System A is dead TRUE as long as system A voltage
is below the level de󰈡ned by
parameter 5820.
02.24 System B is dead System B is dead TRUE as long as system B voltage
is below the level de󰈡ned by
parameter 5820.
02.25 Gen. is mains par. Indicates generator is in mains
parallel operation
TRUE if system A (B) is mains
connected and system B (A) is
variable and CBA is closed and at
least one GCB (easYgen) at a
relevant segment is closed. (It
can be used to enable mains
decoupling.)
02.28 Sync. check relay Indicates phase matching or Dead
Bus conditions met
TRUE if synchronization
conditions are TRUE de󰈡ned by
parameters 5711, 5712, 5710,
8825, 8824, 5712, 5714 and 5717
OR if Dead Bus conditions are
TRUE de󰈡ned by parameters
3432, 5820, 8805, 8802, 8803
and 8804.
Warning
No dead bus interlocking.
02.29 Sync. condition Indicates phase matching
conditions met
TRUE if synchronization
conditions are TRUE de󰈡ned by
parameters 5711, 5712, 5710,
8825, 8824, 5712, 5714 and
5717.
02.30 Dead bus cl. cond. Indicates Dead Bus conditions
met
TRUE if Dead Bus conditions are
TRUE de󰈡ned by parameters
410 LS-5 v2 Series 37650
9 Appendix
9.3 LogicsManager Reference
Released