No. Name Function Note
3432, 5820, 8805, 8802, 8803
and 8804.
Warning
No dead bus interlocking.
9.3.4.4 Group 04: Applications Condition
Applications condition
Logic command variables 4.01-04.63
These operating statuses may be used as command variable in a logical output to set
parameters for customized operations.
No. Name Function Note
04.01 Operat. mode AUTO AUTOMATIC operating mode
active
TRUE in AUTOMATIC operating
mode
04.03 Operat. mode MAN MANUAL operating mode active TRUE in MANUAL operating mode
04.04 Lamp test A lamp test is being performed TRUE if the lamp test is active
04.05 Acknowledge "Acknowledge" push button has
been pressed or an external
acknowledgment via
LogicsManager
This condition is TRUE for approx.
40 ms and must be extended
utilizing a delay time
04.06 Iso.sw./ CBB closed Isolation switch / CBB is closed TRUE if DI 5 (Reply isolation
switch / CBB) is de-energized
04.07 CBA is closed CBA is closed only TRUE if DI 8 (Reply CBA) is de-
energized
04.11 Mains settling Mains settling time active TRUE in LS5 or single LS5 mode
while mains settling time is
running.
04.18 Synchron. CBB active Synchronization CBB is active TRUE if the CBB shall be
synchronized until the CBB is
closed
04.19 Opening CBB active Opening CBB is active TRUE if an CBB open command is
issued until DI 5 (Reply CBB) is
energized
04.20 Closing CBB active Closing CBB is active TRUE if an CBB close command is
issued; same function as relay 4
04.21 Syn. CBA is active Synchronization CBA is active TRUE if the CBA shall be
synchronized until the CBA is
closed
04.22 Opening CBA active Opening CBA is active TRUE if an CBA open command is
issued until DI 8 (Reply CBA) is
energized
04.23 Closing CBA active Closing CBA is active TRUE if an CBA close command is
issued; same function as relay 5
or 6 (cf. parameter 8800)
04.28 Unloading CBB CBB unloading sequence is active TRUE if CBB open with unloading
is active.
04.29 Unloading CBA CBA unloading sequence is active TRUE if CBA open with unloading
is active.
411LS-5 v2 Series37650
9 Appendix
9.3 LogicsManager Reference