Terminal Description A
max
C 54 0 Vdc 2.5 mm²
Tab. 4: Power supply - terminal assignment
Characteristics
Fig. 23: Power supply - crank waveform
3.3.4
Voltage Measuring
General notes
NOTICE!
Incorrect readings due to improper setup
The control unit will not measure voltage correctly if the 120 V and 480 V inputs are
utilized simultaneously.
• Never use both sets of voltage measuring inputs.
Woodward recommends protecting the voltage measuring inputs with slow-acting fuses
rated for 2 to 6 A.
3.3.4.1
Breaker interaction
The drawing below shows a typical example how the LS-5x2 v2 is connected. An isolation
switch like the LS-5x1 is not supported.
43LS-5 v2 Series37650
3 Installation
3.3 Setup Connections