Message text
ID
Meaning
The checksum of the own parameters does not match with the checksum of the majority of
the VDE-AR-N 4105 device partners within 6 s.
Bat. overvoltage 1
10007
Battery overvoltage, limit value 1
The battery voltage has exceeded the limit value 1 for battery overvoltage for at least the
congured time and did not fall below the value of the hysteresis.
Bat. overvoltage 2
10008
Battery overvoltage, limit value 2
The battery voltage has exceeded the limit value 2 for battery overvoltage for at least the
congured time and did not fall below the value of the hysteresis.
Bat. undervoltage 1
10005
Battery undervoltage, limit value 1
The battery voltage has fallen below the limit value 1 for battery undervoltage for at least
the congured time and has not exceeded the value of the hysteresis.
Bat. undervoltage 2
10006
Battery undervoltage, limit value 2
The battery voltage has fallen below the limit value 2 for battery undervoltage for at least
the congured time and has not exceeded the value of the hysteresis.
CANopen Interface 1
10087
Interface alarm CANopen on CAN bus 1
No Receive Process Data Object (RPDO) is received within the congured time.
CBA fail to close
2623
CBA failed to close
The LS-5 has attempted to close the CBA the congured maximum number of attempts and
failed. The LS-5 will continue to attempt to close the CBA as long as the conditions for
closing the CBA are fullled.
CBA fail to open
2624
Failed CBA open
The LS-5 is still receiving the reply CBA closed after the CBA open monitoring timer has
expired.
CBA syn. timeout
3074
CBA synchronization time exceeded
The LS-5 has failed to synchronize the CBA within the congured synchronization time.
CBA unload mismatch
8838
CBA unloading mismatch
While unloading CBA the dened limit of load is not reached in the dened time.
CBB fail to close
2603
CBB failed to close
The LS-5 has attempted to close the CBB the congured maximum number of attempts and
failed. The LS-5 will continue to attempt to close the CBB as long as the conditions for
closing the CBB are fullled.
CBB fail to open
2604
Failed CBB open
The LS-5 is still receiving the reply CBB closed after the CBB open monitoring timer has
expired.
CBB syn. timeout
3064
CBB synchronization time exceeded
The LS-5 has failed to synchronize the CBB within the congured synchronization time.
CBB unload mismatch
3124
CBB unloading mismatch
While unloading CBB the dened limit of load is not reached in the dened time.
437LS-5 v2 Series37650
9 Appendix
9.4 Event And Alarm Reference