Meaning
The checksum of the own parameters does not match with the checksum of the majority of
the VDE-AR-N 4105 device partners within 6 s.
Bat. overvoltage 1
10007
Battery overvoltage, limit value 1
The battery voltage has exceeded the limit value 1 for battery overvoltage for at least the
con󰈡gured time and did not fall below the value of the hysteresis.
Bat. overvoltage 2
10008
Battery overvoltage, limit value 2
The battery voltage has exceeded the limit value 2 for battery overvoltage for at least the
con󰈡gured time and did not fall below the value of the hysteresis.
Bat. undervoltage 1
10005
Battery undervoltage, limit value 1
The battery voltage has fallen below the limit value 1 for battery undervoltage for at least
the con󰈡gured time and has not exceeded the value of the hysteresis.
Bat. undervoltage 2
10006
Battery undervoltage, limit value 2
The battery voltage has fallen below the limit value 2 for battery undervoltage for at least
the con󰈡gured time and has not exceeded the value of the hysteresis.
CANopen Interface 1
10087
Interface alarm CANopen on CAN bus 1
No Receive Process Data Object (RPDO) is received within the con󰈡gured time.
CBA fail to close
2623
CBA failed to close
The LS-5 has attempted to close the CBA the con󰈡gured maximum number of attempts and
failed. The LS-5 will continue to attempt to close the CBA as long as the conditions for
closing the CBA are ful󰈡lled.
CBA fail to open
2624
Failed CBA open
The LS-5 is still receiving the reply CBA closed after the CBA open monitoring timer has
expired.
CBA syn. timeout
3074
CBA synchronization time exceeded
The LS-5 has failed to synchronize the CBA within the con󰈡gured synchronization time.
CBA unload mismatch
8838
CBA unloading mismatch
While unloading CBA the de󰈡ned limit of load is not reached in the de󰈡ned time.
CBB fail to close
2603
CBB failed to close
The LS-5 has attempted to close the CBB the con󰈡gured maximum number of attempts and
failed. The LS-5 will continue to attempt to close the CBB as long as the conditions for
closing the CBB are ful󰈡lled.
CBB fail to open
2604
Failed CBB open
The LS-5 is still receiving the reply CBB closed after the CBB open monitoring timer has
expired.
CBB syn. timeout
3064
CBB synchronization time exceeded
The LS-5 has failed to synchronize the CBB within the con󰈡gured synchronization time.
CBB unload mismatch
3124
CBB unloading mismatch
While unloading CBB the de󰈡ned limit of load is not reached in the de󰈡ned time.