1Ph 2W Wiring terminals
Phase L1 L2 --- --- L1 L2 --- ---
For di󰈠erent voltage systems, di󰈠erent wiring terminals have to be used.
3.3.5
Current Measuring
Current measuring is available for all three phases of System A.
System B current measuring enables one phase to be measured.
3.3.5.1 Current Measuring (System A)
General notes
WARNING!
Dangerous voltages due to missing load
Before disconnecting the device, ensure that the current transformer (CT) is short-
circuited.
Generally, one line of the current transformers secondary must be grounded close to the
CT.
58 LS-5 v2 Series 37650
3 Installation
3.3 Setup Connections