Wiring terminals
Phase L1 L2 L3 s1 (k) L1 s2 (l) L1 s1 (k) L2 s2 (l) L2 s1 (k) L3 s2 (l) L3
Phase L1 and L3 s1 (k) L1 s2 (l) L1 — — s1 (k) L3 s2 (l) L3
"Phase L1 and L3" applies if the system A voltage measurement is congured to 1Ph 3W
(╚═▷ “3.3.4.2.4 Parameter Setting '1Ph 3W' (1-phase, 3-wire)”).
3.3.5.1.2
Parameter Setting 'Phase L1' 'Phase L2' 'Phase L3'
Schematic and terminals
L1
L2
N
L3
I
SyA L1
L1
L2
N
L3
I
SyA L2
L1
L2
L3
I
SyA L3
Phase L1
Phase L2
Phase L3
N
Fig. 51: Current measuring - system A, 'Phase L1' 'Phase L2' 'Phase L3'
Wiring terminals
F E D C B A
Terminal 1 2 3 4 5 6
Phase L1 s1 (k) L1 s2 (l) L1 — — — —
Phase L2 — — s1 (k) L2 s2 (l) L2 — —
Phase L3 — — — — s1 (k) L3 s2 (l) L3
3.3.5.2 Current Measuring (System B)
General notes
WARNING!
Dangerous voltages due to missing load
• Before disconnecting the device, ensure that the current transformer (CT) is short-
circuited.
60 LS-5 v2 Series 37650
3 Installation
3.3 Setup Connections