Code level
Code level CL0 (User Level)
Standard password = none
This code level permits for monitoring of the system and limited access
to the parameters.
Conguration of the control is not permitted.
Only the parameters for setting the language, the date, the time, and
the horn reset time are accessible.
The unit powers up in this code level.
Code level CL1 (Service Level)
Standard password = "0 0 0 1"
This code level entitles the user to change selected non-critical
parameters, such as setting the parameters accessible in CL0 plus Bar/
PSI, °C/°F.
The user may also change the password for level CL1.
Access granted by this password expires two hours after the password
has been entered and the user is returned to the CL0 level.
Code level CL2 (Temporary
Commissioning Level)
No standard password available
This code level grants temporary access to most of the parameters. The
password is calculated from the random number generated when the
password is initially accessed.
It is designed to grant a user one-time access to a parameter without
having to give him a reusable password. The user may also change the
password for level CL1.
Access granted by this password expires two hours after the password
has been entered and the user is returned to the CL0 level. The
password for the temporary commissioning level may be obtained from
the vendor.
Code level CL3 (Commissioning
Level)
Standard password = "0 0 0 3"
This code level grants complete and total access to most of the
parameters. In addition, the user may also change the passwords for
levels CL1, CL2 and CL3.
Access granted by this password expires two hours after the password
has been entered and the user is returned to the CL0 level.
Once the code level is entered, access to the conguration menus will be permitted for
two hours or until another password is entered into the control. If a user needs to exit a
code level then code level, CL0 should be entered. This will block unauthorized
conguration of the control.
A user may return to CL0 by allowing the entered password to expire after two hours or
by changing any one digit on the random number generated on the password screen and
entering it into the unit.
It is possible to disable expiration of the password by entering "0000" after the CL1 or
CL3 password has been entered. Access to the entered code level will remain enabled
until another password is entered. Otherwise, the code level would expire when loading
the standard values (default 0000) via ToolKit.
Code level display
The current code level is indicated by the corresponding numeric value (e.g. »Code level
display«: »1«) in the conguration menu screens. The value indicates that all parameters
of a higher code level are "locked".
ID Parameter CL Setting range
[Default]
Description
81LS-5 v2 Series37650
4 Conguration
4.1 Basic Setup