state of this switch may be used as a
command variable for the
LogicsManager (02.10).
5816 Hysteresis upper frequency limit 2 0 to 50 %
[0.5 %]
If the system A frequency has
exceeded the limit congured in
parameter 5812, the frequency must
fall below the limit and the value
congured here, to be considered as
being within the operating limits
again.
5813 Lower frequency limit 2 50.0 to 100.0 %
[95.0 %]
The maximum permissible negative
deviation of the system A frequency
from the rated system frequency
(parameter 1750) is congured here.
This value may be used as a
frequency limit switch. The conditional
state of this switch may be used as a
command variable for the
LogicsManager (02.10).
5817 Hysteresis lower frequency limit 2 0 to 50 %
[0.5 %]
If the system A frequency has fallen
below the limit congured in
parameter 5811, the frequency must
exceed the limit and the value
congured here, to be considered as
being within the operating limits
again.
4.3.1.2
System A Decoupling
General notes
The system A decoupling function is intended for use in a mains parallel operation and
monitors a series of subordinate mains protection thresholds. If a threshold is exceeded,
the LS-5 initiates a breaker opening and separates the system B from the mains at the
dened breaker.
The mains decoupling can be fully maintained by the LS-5 device as long no mains
decoupling according to VDE-AR-N 4105 is required. If mains decoupling according to
VDE-AR-N 4105 is required, please refer to ╚═▷ “6.5 Setup VDE-AR-N 4105 Applications”.
The following thresholds are monitored:
• Overfrequency level 1 (╚═▷ “4.3.1.5 System A Overfrequency (Levels 1 & 2) ANSI#
81O”)
• Overfrequency level 2 (╚═▷ “4.3.1.5 System A Overfrequency (Levels 1 & 2) ANSI#
81O”)
• Underfrequency level 1 (╚═▷ “4.3.1.6 System A Underfrequency (Level 1 & 2) ANSI#
81U”)
• Underfrequency level 2 ╚═▷ “4.3.1.6 System A Underfrequency (Level 1 & 2) ANSI#
81U”()
•
Overvoltage level 1 if parametrized for decoupling (╚═▷ “4.3.1.7 System A
Overvoltage (Level 1 & 2) ANSI# 59”)