functions is triggered, the CBB will be
opened.
CBB -> CBA System A decoupling is carried out
according to the following parameters.
If one of the subordinate monitoring
functions is triggered, the CBB will be
opened. If the reply "CBB open" is not
present within the delay con󰈡gured,
the CBA will be opened as well.
CB by LM System A decoupling is carried out
according to the following parameters.
If one of the subordinate monitoring
functions is triggered, a breaker will
be opened, which is determined by
the LogicsManager equation "System
A decoupling CBB"
(parameter
15160). If its status is
TRUE, the CBB will be opened. If its
status is FALSE, the CBA will be
opened.
3113 SyA. decoupling feedback delay 2 0.2 to 99.9 s
[0.4 s]
When the decoupling function is
triggered the con󰈡gured breaker
(parameter 3110) has to be opened. If
the breaker open feedback is not
detected within the time con󰈡gured
here, the other breaker will be
opened.
Notes
This parameter is only valid in SyA.
decoupling modes CBA -> CBB and
CBB -> CBA (parameter 3110)
15160 SyA. decoupl. CBB 2 Determined by
LogicsManager
LogicsManager determines which
breaker will be opened for decoupling.
If 24.73 "LM SyA. decoupl.CBB" is true
the CBB will be opened else the CBA.
Notes
Only valid if "SyA. decoupling"
(parameter 3110) is set to "CB by LM".
For information on the LogicsManager
and its default settings see ╚═▷ “9.3.1
LogicsManager Overview”.
3111 Alarm class 2 A/B/C/D/E/F/Control
[B]
Each limit may be assigned an
independent alarm class that speci󰈡es
what action should be taken when the
limit is surpassed.
For additional information refer to ╚═▷
“9.4.1 Alarm Classes”.
3112 Self acknowledge 2 Yes The control unit automatically clears
the alarm if the fault condition is no
longer detected.
[No] The control unit does not
automatically reset the alarm when
the fault condition is no longer
detected.
99LS-5 v2 Series37650
4 Con󰈡guration
4.3 Con󰈡gure Monitoring
Released