46 Freedom X Owner’s Guide
Adjusting Feature Settings in Configuration Mode
Settings
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
Inverter Ignition Control
, ,
See “Description of Ignition Control Features” on page 31.
LBCO Voltage
. . to .
The voltage setting value can be adjusted by 0.1 increments. The low
battery warning is triggered at LBCO voltage + 0.5
volts. The low battery
warning goes away at LBCO voltage + 1.0 volts.
LBCO Shutdown Delay
Timer
to
When the range is from 1 to 20, the timer setting value can be adjusted by
1-second increments. When the range is from 20 to 300, the timer setting
value can be adjusted by 10-second increments.
LBCO Recovery Voltage
. . to .0
The range is from LBCO voltage + 0.5 to 16, adjusted by 0.1 increments.
Selecting a higher value than the battery’s actual fully-charged voltage
level will not activate the auto-recovery feature. You may manually reset
the inverter when the low battery cut off event occurs.
Power Save Time
, to
The range is from 1 to 25, adjusted by 1-hour increments. The next setting
after 25 is OFF.
Power Save (Load Sensing)
Mode
(enable),
(disable)
When enabled, the inverter’s “no load” loss can be reduced further when
total load is less than 25 watts.
Output Frequency
,
After changing the output frequency setting, turn the unit off and then on
again, in order for the change to take effect.
Output Voltage
, ,
Freedom X Series INV Owners Guide.book Page 46 Tuesday, June 27, 2017 4:10 PM