975-0787-01-01 59
Warning Messages
For error code : after the LBCO shutdown delay, the unit
will immediately stop inverting
For error codes  to : the unit will stop inverting
 Low battery voltage detected
depending on setting, see
“Operating Limits” on page 54.
Battery mode (inverting) Check battery status and recharge if necessary.
Check for proper DC cable sizing.
Check for loose connections and tighten if necessary.
 AC output overload warning Battery mode (inverting) Reduce the loads connected to the AC outlet of the unit.
 Over-temperature alarm and
fan lock alarm
Battery mode (inverting) Reduce the loads connected to the AC outlet of the unit.
Check that the ventilation grille is not blocked.
Check for ambient temperature and move the unit to a cooler
location whenever possible.
Check the fan for any obstruction and remove it.
 Fan lock error Battery and grid modes If there is no issue with the fan, disconnect the unit from its DC and
AC power sources, then reconnect, and then restart the unit. Perform
“Step 8: Testing Your Installation” on page 33.
If error detection persists, contact customer service.
 to  Internal hardware error Battery and grid modes If error detection persists, contact customer service.
Table 6 Error Codes Displayed on the LCD Screen
Error Code Condition Mode Action
Freedom X Series INV Owners Guide.book Page 59 Tuesday, June 27, 2017 4:10 PM