Adjusting Settings in Configuration Mode
56 Freedom XC Owner's Guide
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
Equalize Charging for
Flooded Battery
27 DIS
ENA (enable)
DIS (disable)
This setting is only available when Flooded battery type is
selected. It allows only one hour of equalize charging once.
AC Input Breaker for
Load Share
28 30 5 to 30
The load share feature prioritizes the AC load by reducing the
charge current in order to maintain the total input current to less
than the load share setting.
Reset all settings to their
default values
99 ndf
NDF (as is)
DEF (default)
ndF refers to current settings.
Choose def to restore all settings to their default values.