Remote Operation
SCPI Commands for Digital Interfaces
Release 3.0 139
Selecting a Trigger Source
If any triggers are programmed into the sequence, select a trigger source:
PROG:TRIG:SOUR {BUS|MAN|EXT|IMM}
BUS - trigger signal is IEEE 488.1 GET or *TRG
MANual - trigger input is from the front panel TRIGGER key
EXTernal - The external trigger line is selected as the source.
IMMediate - The source is the SCPI command “INIT:IMM”
Editing Step Parameters
Commands are provided to edit only one of voltage, current, power, OVP level, step
duration, or end action.
Program step voltage: PROG:STEP<step_number>:VOLT <voltage>
Program step current: PROG:STEP<step_number>:CURR <current>
Program step power: PROG:STEP<step_number>:POW <power>
Program step OVP level: PROG:STEP<step_number>:OVP
<OVPlevel>
Program step time (duration): PROG:STEP<step_number>:DWEL
{<time>|TRIG}
To dele te a step:
PROGram:STEP<step_number>:DELete
An error will result if the last step with the end action is deleted, without a new end
action programmed to take its place.
Deleting Sequences
If you no longer need a sequence, select it with the PROG:NAME command and then
delete it with the following:
PROGram:DELete
You can also use the following to delete all sequences:
PROGram:DELete:ALL