Installation
Load Connection
46 Operating Manual for XHR Series Power Supply
Radial Power Distribution Method To connect distributed loads, we
recommend that you use radial power distribution. With this method, you connect
power to each load individually from a single pair of terminals designated as the
positive and negative distribution terminals. These terminals may be the power
supply output terminals, the terminals of one of the loads, or a distinct set of
terminals especially established for distribution use. Connect the sense leads to these
terminals to compensate for losses and minimize the effect of one load upon another.
Figure 2.8 and Figure 2.9 show recommended load and sensing connections for
multiple loads. Local sense lines shown are default J2 connections. Refer to Using
Remote Sensing for how to ground the sense line shield.
Figure 2.8 Multiple Loads with Local Sensing