Troubleshooting
4–4 975-0555-01-01
9
N/A Low output voltage
on a true RMS
reading voltmeter.
Low input voltage and the
load is close to maximum
allowable power.
Check the connections and DC
cables and check if the battery
is fully charged. Recharge the
battery if it is low.
Reduce the load.
10
N/A No AC output
voltage; no DC input
voltage indication.
The inverter is off.
No power to the inverter.
Battery disconnect switch
or breaker is off.
Turn the inverter on.
Check if the DC cables are
connected from battery to the
inverter.
Close battery disconnect switch
or breaker.
11
N/A No AC output
voltage; there is DC
input voltage
indication.
20 A supplementary
protector tripped.
The inverter could have
been connected with
reverse DC input polarity.
GFCI may have tripped.
Reduce the AC load and reset
the supplementary protector by
pressing the reset button.
The inverter has been damaged.
Return the inverter. See the
Warranty section for return
information.
Note: Damage caused by
reverse polarity is not covered
by the warranty.
Reset the GFCI.
Table 4-1
Troubleshooting Reference
#
Error/Warning
Code on Display Problem Possible Cause Solution